CO2 monitor for measurement of ventilation in closed environments, COVID-19 prevention, and improvement of work performance

Monitor de CO2 para medida de la ventilación en ambientes cerrados, prevención del COVID-19 y mejora del rendimiento laboral

Authors

Keywords:

gas sensors, environmental monitoring, COVID-19, data processing, carbon dioxide (en).

Keywords:

sensores de gas, monitoreo ambiental, COVID-19, procesamiento de datos, dióxido de carbono (es).

Downloads

Abstract (en)

Objective: Humans produce and exhale CO2, thus the concentration of this gas increases in closed environments. The CO2 concentration of air is often used as a reference to measure the ventilation rate. The typical outdoor CO2 concentration is approximately 400 ppm, although it can be as high as 500 ppm. Concentrations greater than 20000 ppm result in deep breathing, higher than 100000 ppm cause visual disturbances and tremors with possible loss of consciousness and over 250000 ppm may cause death. In buildings with no change on their ventilation rate, high CO2 concentrations have negative effects on decision making and working performance. At 1000 ppm, performance is significantly reduced in six of nine decision-making metrics compared to 600 ppm. In this work, a CO2 flexible monitor is designed to measure ventilation in closed environments.


Methodology: Electrolytic and infrared CO2 sensors with a detection range of 350 to up to 10000 ppm were used. The used sensors have good sensitivity and selectivity to CO2. The gas monitor has a simple calibration system, whereby softwareautomatically adjusts the calibration curve parameters after circulating clean air. The design of a gas bench used to verify sensor calibration is also shown.


Results: A set of measurements were performed with electrochemical gas sensors and infrared (IR) gas sensors to test the functionality of the equipment. Experimental work has shown sensors have a satisfactory response for this application. The margins of error are +5 % of the reading value.


Conclusions: A low cost, flexible gas monitor for indoor environments like schools, offices, laboratories, and industries was designed in this work. Due to the flexible design, a network of gas monitors strategically distributed in the different spaces of the buildings is proposed.


Fundings: Universidad Tecnológica Nacional. Comisión Nacional de Energía Atómica. Buenos Aires, Argentina 

Abstract (es)

Objetivo: Los humanos producimos y exhalamos CO2, por lo que la concentración de este gas aumenta en ambientes cerrados. La concentración de gas CO2 en el aire se utiliza a menudo como referencia para medir la tasa de ventilación. La concentración típica de CO2 al aire libre es de aproximadamente 400 ppm, aunque puede llegar a 500 ppm. Las concentraciones superiores a 20000 ppm dan como resultado una respiración profunda, superiores a 100000 ppm provocan alteraciones visuales y temblores con posible pérdida del conocimiento y superiores a 250000 ppm pueden provocar la muerte. En edificios sin cambios en su tasa de ventilación, las altas concentraciones de CO2 tienen efectos negativos en la toma de decisiones y el rendimiento laboral. A 1000 ppm, el rendimiento se reduce significativamente en seis de las nueve métricas de toma de decisiones en comparación con 600 ppm. En este trabajo se diseña un monitor flexible de CO2 para medir la ventilación en ambientes cerrados.


Metodología: Se utilizaron sensores de CO2 electrolíticos y sensores infrarrojos con un rango de detección de 350 hasta 10000 ppm. Los sensores utilizados tienen buena sensibilidad y selectividad al CO2. El monitor de gas tiene un sistema de calibración simple, mediante el cual el software ajusta automáticamente los parámetros de la curva de calibración después de hacer circular aire limpio. También se muestra el diseño de un banco de gases utilizado para verificar la calibración del sensor.


Resultados: Se realizaron un conjunto de mediciones, con sensores de gases electrolíticos químicos y sensores de gases infrarrojos (IR) probando la funcionalidad del equipo. El trabajo experimental ha demostrado que los sensores tienen una respuesta satisfactoria para esta aplicación. Los márgenes de error son 5 % del valor de lectura.


Conclusiones: En este trabajo se diseñó un monitor de gas flexible y de bajo costo para ambientes interiores como escuelas, oficinas, laboratorios e industrias. Debido al diseño flexible, se propone una red de monitores de gas distribuidos estratégicamente en los distintos espacios de los edificios.


Financiamiento: Universidad Tecnológica Nacional. Comisión Nacional de Energía Atómica. Buenos Aires, Argentina.

 

Author Biographies

Juan Vorobioff, Universidad Tecnológica Nacional

Ingeniero Electrónico, Doctor en Ingeniería, Mención Procesamiento de Señales e Imágenes. Profesor en FRBA Universidad Tecnológica Nacional. Investigador en Comisión Nacional de Energía Atómica. Buenos Aires, Argentina

Norberto Gabriel Boggio, Universidad Nacional de San Martín

Licenciado en Química, doctor en Ingeniería de Microsistemas, investigador del Instituto de Nanociencia y Nanotecnología (INN-Conicet). Profesor de la Universidad Nacional de San Martín, Buenos Aires, Argentina

Federico Ricardo Checozzi, Comisión Nacional de Energía Atómica

Ingeniero Electrónico. Investigador de la Comisión Nacional de Energía Atómica. San Martín, Argentina.

Tamara Pinto Garrón, Universidad Tecnológica Nacional

Bachiller en gestión y administración de las organizaciones. Estudiante de Ing. Química en FRBA Universidad Tecnológica Nacional, Argentina.

Carlos Rinaldi, Comisión Nacional de Energía Atómica

Licenciado en Química. Doctor en Química. CONICET, Instituto de Tecnologías Emergentes y Ciencias Aplicadas, Profesor en Universidad Nacional de San Martín. Comisión Nacional de Energía Atómica. Buenos Aires, Argentina.

References

Acosta Pérez, M. A., Suárez Castrillón, S. A., & Suárez Castrillón, A. M. (2016). Desarrollo y ensayo de un sensor químico de fibra óptica para la medición de concentraciones de dióxido de carbono. Revista Tecnura, 20(50). https://revistas.udistrital.edu.co/index.php/Tecnura/article/view/11558/12386

Allen, J. G., MacNaughton, P., Satish, U., Santanam, S., Vallarino, J., & Spengler, J. D. (2016). Associations of cognitive function scores with carbon dioxide, ventilation, and volatile organic compound exposures in office workers: A controlled exposure study of green and conventional office environments. Environmental Health Perspectives, 124(6). https://doi.org/10.1289/ehp.1510037

Chen, C. Y., Chen, P. H., Chen, J. K., & Su, T. C. (2021). Recommendations for ventilation of indoor spaces to reduce COVID-19 transmission. In Journal of the Formosan Medical Association (Vol. 20, Issue 12). https://doi.org/10.1016/j.jfma.2021.08.007

Di Gilio, A., Palmisani, J., Pulimeno, M., Cerino, F., Cacace, M., Miani, A., & de Gennaro, G. (2021). CO2 concentration monitoring inside educational buildings as a strategic tool to reduce the risk of Sars-CoV-2 airborne transmission. Environmental Research, 202. https://doi.org/10.1016/j.envres.2021.111560

Díaz, C. M. M. (2021). Gestión ambiental: In Lecturas medio ambiente t. VIII. https://doi.org/10.2307/j.ctv25tnwb0.12

Freire-Vinueza, C., Meneses, K., & Cuesta, G. (2021). América Latina: ¿Un paraíso de la contaminación ambiental? Revista de Ciencias Ambientales, 55(2). https://www.scielo.sa.cr/pdf/rca/v55n2/2215-3896-rca-55-02-1.pdf

García Alvarado, R., Herrera Ojeda, R., Muñoz Viveros, C., & Wandersleben, G. (2016). Desempeño ambiental de recintos habitacionales. Comparación de simulaciones, monitorización y percepción de residentes en seis viviendas de Concepción, Chile. Revista Tecnura, 20(47). https://doi.org/10.14483/udistrital.jour.tecnura.2016.1.a06

Gil-Baez, M., Lizana, J., Becerra Villanueva, J. A., Molina-Huelva, M., Serrano-Jimenez, A., & Chacartegui, R. (2021). Natural ventilation in classrooms for healthy schools in the COVID era in Mediterranean climate. Building and Environment, 206. https://doi.org/10.1016/j.buildenv.2021.108345

Li, C., & Tang, H. (2021). Study on ventilation rates and assessment of infection risks of COVID-19 in an outpatient building. Journal of Building Engineering, 42. https://doi.org/10.1016/j.jobe.2021.103090

Massacane, A., Vorobioff, J., Pierpauli, K., Boggio, N. G., Reich, S., Rinaldi, C. A., Boselli, A., amagna, A., Azcárate, M. L., Codnia, J., & Manzano, F. (2010). Increasing electronic nose recognition ability by sample laser irradiation. Sensors and Actuators, B: Chemical, 146(2). https://doi.org/10.1016/j.snb.2009.12.033

Ostro, B. D., Broadwin, R., & Lipsett, M. J. (2000). Coarse and fine particles and daily mortality in the Coachella Valley, California: A follow-up study. Journal of Exposure Analysis and Environmental Epidemiology, 10(5). https://doi.org/10.1038/sj.jea.7500094

Persily, A., & de Jonge, L. (2017). Carbon dioxide generation rates for building occupants. Indoor Air, 27(5). https://doi.org/10.1111/ina.12383

Quesada Carvajal, L. V., Pino Gomez, M., & Elizondo Hernández, R. (2018). Estimación emisiones de compuestos orgánicos volátiles, plantel de distribución de combustibles Recope, el Alto de Ochomogo, Cartago, Costa Rica. Tecnura, 22(55). https://doi.org/10.14483/22487638.12543

Rodríguez, D., Bonaparte, J., Boggio, N., & Fasciszewski, A. (2019). Desarrollo y fabricación de un microsensor de gas de baja potencia para la detección de amoniaco a bajas concentraciones. Tecnura, 23(61). https://doi.org/10.14483/22487638.15353

Sanchez Quintero, T., Gómez Santamaría, C., & Hincapié Reyes, R. C. (2021). Localización de múltiples fuentes basada en información de dirección de llegada mediante el uso de la teoría de sensado comprimido de la posición basado en información de dirección de llegada aplicando sensado comprimido a la matriz de covarianza. Tecnura, 25(67). https://doi.org/10.14483/22487638.16302

Satish, U., Mendell, M. J., Shekhar, K., Hotchi, T., Sullivan, D., Streufert, S., & Fisk, W. J. (2012). Is CO2 an indoor pollutant? direct effects of low-to-moderate CO2 concentrations on human decisionmaking performance. Environmental Health Perspectives, 120(12). https://doi.org/10.1289/ehp.1104789

Shen, Chen. (2014). An Investigation of a Low-cost CO2 Indoor Air Quality Monitor. https://www.researchgate.net/publication/273770363_An_Investigation_of_a_Low-cost_CO2_Indoor_Air_Quality_Monitor.

Schibuola, L., & Tambani, C. (2021). High energy efficiency ventilation to limit COVID-19 contagion in school environments. Energy and Buildings, 240. https://doi.org/10.1016/j.enbuild.2021.110882

Tusman, G., Campos, M., & Gogniat, E. (2020). COVID-19: how to transform a noninvasive ventilation device in a critical care ventilator. Revista Espanola de Anestesiologia y Reanimacion, 67(7). https://doi.org/10.1016/j.redar.2020.05.002

Vorobioff, J., Boggio, N., Gutierrez, M., Checozzi, F., & Rinaldi, C. (2020). Design of drones for monitoring of volcanic areas. Tecnura, 24(66). https://doi.org/10.14483/22487638.16800

Zivelonghi, A., & Lai, M. (2021). Mitigating aerosol infection risk in school buildings: the role of natural ventilation, volume, occupancy and CO2 monitoring. Building and Environment, 204. https://doi.org/10.1016/j.buildenv.2021.108139

How to Cite

APA

Vorobioff, J., Boggio, N. G., Checozzi, F. R., Pinto Garrón, T., and Rinaldi, C. (2024). CO2 monitor for measurement of ventilation in closed environments, COVID-19 prevention, and improvement of work performance. Tecnura, 27(78), 142–156. https://doi.org/10.14483/22487638.19522

ACM

[1]
Vorobioff, J. et al. 2024. CO2 monitor for measurement of ventilation in closed environments, COVID-19 prevention, and improvement of work performance. Tecnura. 27, 78 (Jul. 2024), 142–156. DOI:https://doi.org/10.14483/22487638.19522.

ACS

(1)
Vorobioff, J.; Boggio, N. G.; Checozzi, F. R.; Pinto Garrón, T.; Rinaldi, C. CO2 monitor for measurement of ventilation in closed environments, COVID-19 prevention, and improvement of work performance. Tecnura 2024, 27, 142-156.

ABNT

VOROBIOFF, Juan; BOGGIO, Norberto Gabriel; CHECOZZI, Federico Ricardo; PINTO GARRÓN, Tamara; RINALDI, Carlos. CO2 monitor for measurement of ventilation in closed environments, COVID-19 prevention, and improvement of work performance. Tecnura, [S. l.], v. 27, n. 78, p. 142–156, 2024. DOI: 10.14483/22487638.19522. Disponível em: https://revistas.udistrital.edu.co/index.php/Tecnura/article/view/19522. Acesso em: 27 jul. 2024.

Chicago

Vorobioff, Juan, Norberto Gabriel Boggio, Federico Ricardo Checozzi, Tamara Pinto Garrón, and Carlos Rinaldi. 2024. “CO2 monitor for measurement of ventilation in closed environments, COVID-19 prevention, and improvement of work performance”. Tecnura 27 (78):142-56. https://doi.org/10.14483/22487638.19522.

Harvard

Vorobioff, J. (2024) “CO2 monitor for measurement of ventilation in closed environments, COVID-19 prevention, and improvement of work performance”, Tecnura, 27(78), pp. 142–156. doi: 10.14483/22487638.19522.

IEEE

[1]
J. Vorobioff, N. G. Boggio, F. R. Checozzi, T. Pinto Garrón, and C. Rinaldi, “CO2 monitor for measurement of ventilation in closed environments, COVID-19 prevention, and improvement of work performance”, Tecnura, vol. 27, no. 78, pp. 142–156, Jul. 2024.

MLA

Vorobioff, Juan, et al. “CO2 monitor for measurement of ventilation in closed environments, COVID-19 prevention, and improvement of work performance”. Tecnura, vol. 27, no. 78, July 2024, pp. 142-56, doi:10.14483/22487638.19522.

Turabian

Vorobioff, Juan, Norberto Gabriel Boggio, Federico Ricardo Checozzi, Tamara Pinto Garrón, and Carlos Rinaldi. “CO2 monitor for measurement of ventilation in closed environments, COVID-19 prevention, and improvement of work performance”. Tecnura 27, no. 78 (July 26, 2024): 142–156. Accessed July 27, 2024. https://revistas.udistrital.edu.co/index.php/Tecnura/article/view/19522.

Vancouver

1.
Vorobioff J, Boggio NG, Checozzi FR, Pinto Garrón T, Rinaldi C. CO2 monitor for measurement of ventilation in closed environments, COVID-19 prevention, and improvement of work performance. Tecnura [Internet]. 2024 Jul. 26 [cited 2024 Jul. 27];27(78):142-56. Available from: https://revistas.udistrital.edu.co/index.php/Tecnura/article/view/19522

Download Citation

Visitas

5

Dimensions


PlumX


Downloads

Download data is not yet available.

Most read articles by the same author(s)

Loading...